0700015-J0 Rev B

76

6.7.2.8 Converter Signals

Use to view the status of all acquired converters in the system; including but not limited to:
Total Conv. Current
Avg Conv. Output Voltage
Total Conv. Input Current
# Acquired Conv.
# Failed Conv.
# Conv. Minor Alarm
# Conv. In Comms Lost
# Conv. Input Voltage Failed
# Out Of Tolerance Conv.
# Conv. In Current Limit
# Conv. Fan Failed
Converter Load Voltage
Converter Load Current
The existing Controller Signals category now includes signals for Converter Load Voltage and Converter

Load Current; by default, Average Conv. Output Voltage and Total Conv. Output Current are used respec-

tively.

Re-configurable System Load Current and System Battery Voltage
For converter shelves that do not have any Cordex rectifiers in the system, the system Load Current can

be re-configured to display the total converter output current and the system Battery Voltage can be re-

configured to display converter output voltage; the signals can also be renamed (see “6.12.2 Customize

User Interface” on page 97).

Recommendation For Converter Redundancy
A redundant converter in a system will allow one converter to be shut down while the other converters

supply power to the load; e.g., during firmware upgrade.

6.7.2.9 Inverters

The Signals submenu enables the user to access inverter signals for all of the acquired inverters in the

system. The following signals can be used for logging and equation building.
AC Output VA
Input Source Ratio (%AC)
AC Output Power
DC Input Currnet
Acquired Inverters
# Inverters in Comms Lost
# Minor Alarm Inverters
# Major Alarm Inverters
# Failed Inverters