The following are new features in Version 3.1x:
• Retrieve inverter history file—see 6.4.8.2)
• Inverter alarms reported in the Event log—see 6.4.8.1
• Synchronization of the real time clock of the inverter controller (T2S) with the Cordex controller RTC
• Support of new CXCi+ hardware

2.1 Password Security

NOTE:

Basic authentication is cached in Firefox and the Panel PC, so that the client is not

prompted to re-enter the password again after logging out. Closing the browser clears the

cache and prevents use by unathorized personnel.

Three levels of password security are available: Supervisor (1234), User (5678) and Viewer (0000). A

Supervisor has write access to all editable fields. A User has permission to update inventory, make volt-

ages changes and navigate through menus. A viewer can view all menus, but does not have permission

to make any changes.
The User password can only changed by the Supervisor from the web interface (see 6.12.1). Viewer login

is described in the next section.

2.1.1 Client Login Control

It is possible to have multiple users logged onto the controller. The following table shows the distribution

of allowed logins. (Both a User and a Supervisor are considered to have write access and only one can

be logged on at a time.)

Web Clients

LCD Clients

(Only 1 person can work with the

LCD)

Number of Viewers

User

or Supervisor

Number of Viewers

User

or Supervisor

1-2

0

1

0

1-2

0

0

1**

1-2

1*

-

-

-

-

-

1**

*

A User or Supervisor login to the web interface prevents any logins at the LCD - a 

viewer currently logged on to the LCD will not be able to log back in if he logs off.

**

A User or Supervisor login to the LCD prevents any logins at the web interface- a 

viewer currently logged on to the web will not be able to log back in if he logs off.

2.2 Software Configuration Loading and Updates

Factory software updates and adjustments to the configuration file are possible through the Ethernet con-

nection. The Supervisor can exclude settings and groups of settings when applying changes. A partial

configuration file can also be generated and sent to the CXC (v1.81 and above).

2.3 Customizable User Interface

The web interface can be customized to remove web browser elements that are of no interest to the user.

This menu for customizing the user interface is located in

Supervisor > Customize User Interface

. When

a group is unchecked, all related UI elements are removed from the browser. This includes menu items,

summary information in the View Live Status and signals and alarms.