Table o — inverter global settings, Table p — inverter parameters – Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 128

Advertising
background image

0700015-J0 Rev B

126

The inverter configuration file is actually one big file, but is presented here as Table P, Table Q, and Table R

for clarity.

Table P — Inverter Global Settings

Submenu Item

Default Setting

Units

Number of module in phase 1

10

Number of module in phase 2

10

Number of module in phase 3

10

Number of module in phase 4

0

Number of module in phase 5

0

Number of module in phase 6

0

Number of module in phase 7

0

Number of module in phase 8

0

Amount of redundancy in phase 1

0

Amount of redundancy in phase 2

0

Amount of redundancy in phase 3

0

Amount of redundancy in phase 4

0

Amount of redundancy in phase 5

0

Amount of redundancy in phase 6

0

Amount of redundancy in phase 7

0

Amount of redundancy in phase 8

0

Number of DC input groups

1

Number of AC input groups

3

Table Q — Inverter Parameters

Submenu Item

Default Setting

Units

Input Source (AC : 0 DC : 100)

0

%

ACin Mode (0 : normal 1 : Safe)

0

Walk-in Mode (0 : NO 1 : YES)

0

Number of phases

1

Mode (0 : star 1 : triangle)

1

Free running Frequency

60.0

Hz

Short Circuit Voltage Threshold

80

V

Short Circuit Hold Time

60.0

s

Booster 10xIin (0 : OFF 1 : ON)

1

Max current (pc of nominal curr)

150

%