Table i — alarms menu defaults – Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 124

Advertising
background image

0700015-J0 Rev B

122

Table J — Alarms menu defaults

Submenu Item

Programmable

Range

Default Setting: Priority, Activation Value

12Vdc

24Vdc

48Vdc

125Vdc

220Vdc

Rectifier Fail

Major/Minor/Message Minor

   Rectifier Minor

Major/Minor/Message Minor

Rect. Major Fail Count

Major/Minor/Message Major, 2

Rect. Minor Fail Count

Major/Minor/Message Minor, 1

   Rectifier Lockout

Major/Minor/Message Minor

Out of Tolerance

Major/Minor/Message Minor

   Rect. Communications Lost

Major/Minor/Message Minor

Rect. Equalize Activated

Major/Minor/Message Minor

Rect. AC Mains Fail

Major/Minor/Message Minor

   Max. Rectifiers Exceeded

Major/Minor/Message Minor

Fan Fail Alarm

Major/Minor/Message Minor

Power Save

Major/Minor/Message

Distribution Fuse (Digital 1)

Major/Minor/Message Minor, High

Battery Fuse (Digital 2)

Major/Minor/Message Major, High

   LVD Manual In (Digital 3)

Major/Minor/Message Minor, High

   LVD Manual Out (Digital 4)

Major/Minor/Message Major, High

Converter Fail (Digital 5)

Major/Minor/Message Minor, High

Conv. I/P Breaker Trip (Digital 6)

Major/Minor/Message Major, High

Digital 7-8

Major/Minor/Message Message, High

Battery Current High

Major/Minor/Message Major, 100A

   Load Current High

Major/Minor/Message Major, 1000A

AC Mains High

Major/Minor/Message Minor,

270V

Minor,

270V

Minor,

270V

Minor,

270V

Minor,

270V

   AC Mains Low

Major/Minor/Message Minor,

180V

Minor,

180V

Minor,

180V

Minor,

180V

Minor,

180V

High Voltage 1

Major/Minor/Message Minor,

14.00V

Minor,

28.00V

Minor,

55.50V

Minor,

134.13V

Minor,

235.88V

High Voltage 2

Major/Minor/Message Major,

14.25V

Major,

29.00V

Major,

56.50V

Major,

136.54V

Major,

240.13V

   Low Voltage 1

Major/Minor/Message Minor,

12.00V

Minor,

24.00V

Minor,

48.00V

Minor,

116.00V

Minor,

204.00V

   Low Voltage 2

Major/Minor/Message Major,

11.62V

Major,

23.25V

Major,

46.50V

Major,

112.38V

Major,

197.63V

Midpoint Monitor 1-5

Major/Minor/Message Minor, 0.50V

Battery Runtime Low

Major/Minor/Message Minor, 3 hours

   Battery Capacity Low

Major/Minor/Message Minor, 80%

Battery Overtemp

Major/Minor/Message Minor, 40ºC

Battery On Discharge

Major/Minor/Message Major

Temp Sensor 1-5 Fail

Major/Minor/Message Message

TC Sensor Fail

Major/Minor/Message Message

Miscellaneous/Real Time Clock Error

Major/Minor/Message Minor

Custom 1-20

See 6.5.3.10

Message

Relay Mapping System Major

See 6.5.3.8

Major, Relay 5

System Minor

See 6.5.3.8

Minor, Relay 4