6.4.7 Auto DC Priority

The inverters can be configured to switch to DC Priority mode when a custom alarm is tripped. The alarm

can be triggered by a digital input such as a signal from an alternative energy source – a fuel cell per-

haps that has just switched on.
When the custom alarm activates, the CXC automatically switches the inverters to draw from DC power

as much as possible. When the alarm is deactivated, the command is sent to return to AC Priority. (Cus-

tom alarms are configured from

Alarms-> Configure Alarms

.)

Figure 47 — Inverters – Auto DC Priority

Figure 48 — Inverters – Auto DC Priority

If the inverters are in DC Priority with the alarm still active, disabling Auto DC Priority does not cause the

inverters to revert to AC. (In addition, this action blocks the alarm input so the inverters will never auto-

matically revert to AC.)
The correct approach is to switch the

Input Source

manually to

AC

in

Inverters > General Settings

. The

manual setting overrides the Auto DC Priority setting.