The following is an example of a Data Log configured to monitor the battery voltage, current, temperature

and other parameters for a battery system.

1. From the web interface, select

Signals > Configure Data Logging

.

2. Under

Data Log Files

, select an unused log file to edit.

3. Enter a filename description under

File Information

.

4. Enter the number of

Log Records

you want to keep and select

FIFO

as the

File Save Option

.

5. Under

Start Trigger

and

Stop Trigger

, select

Manual

for each.

6. Under

Log Frequency

, select

Enable Signal Interval

.

7. Click the

Log Signals

button to select the battery signals for logging.

8. Select

Controller Signals

from the Signal List in the Configure Signals window.

9. Scroll down and check each battery signal as shown.

10. Select

Apply

(to accept changes and return to Configure Data Logging window).

11. Click the

Save

icon to save the changes and click

Accept

when prompted.

12. Start the log by clicking the

Start

button located next to the File Information heading (see Figure 90).

Once the data has collected for the desired interval, return to this window and click the

Stop

button.

13. Select

Logs & Files > Retrieve Logs

. Select the file name from the pull-down menu and then select

Data Log

to view the log information in a new window. Copy and paste the data into a spreadsheet

application for analysis.

Figure 97 — Configure (Signals) Data Logging web interface window, example two

Figure 98 — Enable (Controller) Signals for Data Logging web interface