Table O — Signals menu defaults

Submenu Item

Programmable Range

Default Setting

Load Voltage (V1)

Decimal precision: 0-3

2

Load Current (I1)

Decimal precision: 0-3

1

Battery Voltage (V2)

Decimal precision: 0-3

2

Battery Current (I2)

Decimal precision: 0-3

1

AC Mains

Decimal precision: 0-3

1

Battery Temperature

Decimal precision: 0-3

2

Temp Comp Sensor 1

Enable/Disable

Disable

Temp Comp Sensor 2

Enable/Disable

Disable

   Temp Comp Sensor 3 (GP1)

Enable/Disable

Disable

   Temp Comp Sensor 4 (GP2)

Enable/Disable

Disable

Battery Runtime

Decimal precision: 0-3

2

Battery Capacity

Decimal precision: 0-3

1

Battery Depth of Discharge (DOD)

Decimal precision: 0-3

1

Analog Inputs

See 6.6.1.1

N/A
Digital Inputs (1-8)

High/Low

Low

Rectifier Signals

See Menu Tree

N/A

Custom Signals (1-20)

Decimal precision: 0-3

2

Signal Units

A, V, W, ºC (ºF)

V

Set by SNMP

Enabled/Disabled

Disabled

Set by Equation

Enabled/Disabled

Enabled