Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 140

Advertising
background image

0700015-J0 Rev B

138

Table U — CXC Modbus PDU address definition for function code 0x03 (read holding registers)

PDU Address

Variable Name

Variable Description

Number of

Bytes

0x018A

Signal_5_In_Signal_Table_5

Timer 5

4 (signed int_32)

0x018C

Signal_6_In_Signal_Table_5

Timer 6

4 (signed int_32)

0x018E

Signal_7_In_Signal_Table_5

Timer 7

4 (signed int_32)

0x0190

Signal_8_In_Signal_Table_5

Timer 8

4 (signed int_32)

0x0192

Signal_9_In_Signal_Table_5

Timer 9

4 (signed int_32)

0x0194

Signal_10_In_Signal_Table_5

Timer 10

4 (signed int_32)

0x01C2

Signal_1_In_Signal_Table_6

Counter 1

4 (signed int_32)

0x01C4

Signal_2_In_Signal_Table_6

Counter 2

4 (signed int_32)

0x01C6

Signal_3_In_Signal_Table_6

Counter 3

4 (signed int_32)

0x01C8

Signal_4_In_Signal_Table_6

Counter 4

4 (signed int_32)

0x01CA

Signal_5_In_Signal_Table_6

Counter 5

4 (signed int_32)

0x01CC

Signal_6_In_Signal_Table_6

Counter 6

4 (signed int_32)

0x01CE

Signal_7_In_Signal_Table_6

Counter 7

4 (signed int_32)

0x01D0

Signal_8_In_Signal_Table_6

Counter 8

4 (signed int_32)

0x01D2

Signal_9_In_Signal_Table_6

Counter 9

4 (signed int_32)

0x01D4

Signal_10_In_Signal_Table_6

Counter 10

4 (signed int_32)

Table V — CXC Modbus PDU address definition for function code 0x04 (read input registers)

PDU

Address

Variable Name

Variable Description

Response

Data

Format

0x0001

Relays_Total (Y)

Read number of relays

BINARY

0x0002

Total_Active_Alarms (Z)

Read total active alarms

BINARY

0x0003

System_Major_Alarm

Read system major alarm status

BINARY

0x0004

System_Minor_Alarm

Read system minor alarm status

BINARY

0x0011

Alarm_Tables_Total (X)

Read number of alarm tables (X<=0x1E)

BINARY

0x0012

Alarms_Total_In_Alarm_Table _1 (A1)

Read number of alarm in alarm table 1 (A1

<= 0x3F)

BINARY

0x0013

Alarms_Total_In_Alarm_Table _2 (A2)

Read number of alarm in alarm table 2 (A2

<= 0x3F)

BINARY

0x0011 + X  Alarms_Total_In_Alarm_Table _X (AX)

Read number of alarm in alarm table X (AX

<= 0x3F)

BINARY

0x0031

Number_of_Active_Alarms_In_Alarm_table _1

Read number of active alarms in alarm

table 1

BINARY

0x0032

Number_of_Active_Alarms_In_Alarm_table _2

Read number of active alarms in alarm

table 2

BINARY

0x0031 + 

(X-1)

Number_of_Active_Alarms_In_Alarm_table _X

Read number of active alarms in alarm

table X

BINARY

Advertising