6.7.3.4 Example One – Logging Three Phase Voltage Input (Rectifier System)

The following is an example of a Data Log configured to monitor the voltage input for a two phase rectifier

system.

1. From the web interface, select

Signals > Configure Data Logging

.

2. Under

Data Log Files

, select an unused log file to edit.

3. Enter a filename description under

File Information

.

4. Enter the number of

Log Records

you want to keep and select

FIFO

as the

File Save Option

.

5. Under

Start Trigger

and

Stop Trigger

, select

Manual

for each.

6. Under

Log Frequency

, select

Enable Time Interval

and enter 600 seconds (10 minutes).

7. Click the

Log Signals

button to select the rectifier signals for logging.

8. Select

Rectifier Signals

from the Signal List in the Configure Signals window.

9. Scroll down and check each phase box as shown.

10. Click the

Apply

tab (to accept changes and return to Configure Data Logging window).

11. Click the

Save

icon to save the changes and click Accept when prompted.

12. Start the log by clicking the

Start

button located next to the File Information heading (see Figure 95.

Once the data has collected for the desired interval, return to this window and click the

Stop

button.

13. Select

Logs & Files > Retrieve Logs

. Select the file name from the pull-down menu and then select

Data Log

to view the log information in a new window. Copy and paste the data into a spreadsheet

application for analysis.

Figure 95 — Configure (Signals) Data Logging web interface window, example one

Figure 96 — Enable (Rectifier) Signals for Data Logging