6.7.2 Configure Signals

This menu item allows the Supervisor to configure Controller Signals (and Analog Inputs described

above). The status of Digital Inputs and Rectifier Signals can also be viewed under this menu (LCD inter-

face only).

6.7.2.1 Controller Signals

Use the Controller Signals menu to access/ edit items such as load current and battery temperature.

See 2.1 (to enable Battery sensors.) Once a menu item is selected, tap the

Configure

button to produce

another window and list of items to navigate and edit. See examples on the next page.

Definitions

Load Voltage

Discharge voltage.

Load Current

Discharge current.

Battery Voltage

Charge or system voltage.

Battery Current

Charge current.

AC Mains

Average rectifier input voltage. AC Correction appears when AC Mains is

selected.

Total Rectifier Current

Sum of rectifier output currents.

Battery Temperature

Average of enabled sensors (if temperature sensors agree within 5%) or

the peak value of enabled sensors (if temperature sensors do not agree

within 5%).

Battery Run Time

Estimated time remaining before LVD.

Battery Capacity

A battery’s estimated ability to store charge.

Battery Depth of
Discharge

Estimate of the energy removed from a battery during a discharge in %.

Converter Load Voltage

Converter output voltage.

Converter Load Current

Converter output current.

The following table summarizes the default controller signal equations:

Table F — Controller signal default definitions

Controller Signals

Signal Equations

Load Voltage

[V1]

Load Current

[I1]

Battery Voltage

[V2]

Battery Current

[Total Rectifier Current] – [Load Current]