Table c — digital input channel assignments, 2 digital alarms – Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 63

Advertising
background image

61

0700015-J0 Rev B

Fan Fail Alarm (for Fan
Cooled Systems)

Triggers an alarm when a fan fail (speed error or failed fan) condition has

occurred in any of the rectifiers in the system.
• The Fan Fail Alarm is true when the CXC receives a Fan Fail or Fan

Speed Error alarm from any rectifier.

• The Fan Fail Alarm is cleared when all Fan Fail and Fan Speed Error

alarms are cleared from all the rectifiers.

• Each time that the Fan Fail Alarm goes on/off, the event is logged in the

Event History. Since it is a rectifier alarm, up to nine rectifiers (up to 27

fan fail alarms) that are in alarm are logged. If more than nine rectifiers

are in alarm an additional entry is made indicating the total number of

rectifiers in alarm.

The activation value is factory set.

Power Save

Sets an alarm condition when a rectifier is in Power Save mode. The

activation value is factory set.

Urgent AC Mains Fail

Sets a major alarm condition when the Rectifier AC Mains Fail alarm has

been active for a period of time; the default activation value is ten (10)

minutes (see 2.1).

6.6.4.2 Digital Alarms

Each digital input channel is designed to detect zero-system voltage (i.e. off/on) signal. Six of the digital

channels have assigned functions, while two are unassigned. Table D summarizes the digital channel

assignments.
Note that the number of digital inputs varies with hardware. the CXCU and CXCI, for example, have six

only.

Table D — Digital input channel assignments

Channel Description

Factory Default Designation

DIG1 (D1 on PCB)

Distribution Fuse/Circuit Breaker

DIG2 (D2 on PCB)

Battery Fuse/Circuit Breaker

DIG3 (D3 on PCB)

LVD Manual In

DIG4 (D4 on PCB)

LVD Manual Out

DIG5 (D5 on PCB)

Converter Fail

DIG6 (D6 on PCB)

Converter I/P Breaker Trip

DIG7 (D7 on PCB)

Digital 7 (unassigned)

DIG8 (D8 on PCB)

Digital 8 (unassigned)

Digital events occurring on one of the digital inputs can be programmed to the output alarm relays using

the programming feature for the relay contact similar to analog alarms.
The status of each digital input is visible under the Signals menu; see “LCD Menu structure” on page 17, or

in the web interface go to

Main Menu > Signals > View Status

.

Tap the Activation Value to edit with

the virtual numeric keypad.

Toggle check boxes to select option.

When selecting SNMP, the severity level

(numeric) can also be set.

Discard changes and return to

previous screen

Relay Mapping – N/A or relay 1 to 16

Priority – Major, Minor or Message.

Accept changes and return to

previous screen

Figure 65 — Configure Urgent AC Mains Fail Example