Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 114

Advertising
background image

0700015-J0 Rev B

112

9.3.2 Computer Setup

1. In Windows® 2000, select

START > SETTINGS

, and then select

NETWORK AND DIAL-UP

CONNECTIONS

.

2. Double-click the

MAKE NEW CONNECTION

icon to start the Network Connection Wizard.

3. Select

DIAL-UP TO PRIVATE NETWORK

. Note: Some systems may come up with another pop-up

selection for modem or infrared port. Modem should be selected.

4. Enter the phone number for the Cordex (this field can be blank and the phone number may be

entered in the pop-up connection window, see note below).

5. Select

FOR ALL USERS

or

ONLY FOR MYSELF

as required. Then select

NEXT

to continue.

6. Select a Unique name for the Cordex connection; for example, “SiteName CXC.modem.” Then select

FINISH

to continue.

NOTE: A dialup connection interface may appear. (If not, enter the phone number as in step 4. If

in Step 5,

FOR ALL USERS

was selected, then there is no need to enter user name and password.

Leave these two fields blank.)

7. Select

PROPERTIES

. Ensure the correct modem appears under

CONNECT USING

. Then select

CONFIGURE

to continue.

8. Change MODEM SPEED (BPS) to 57600. Deselect all

HARDWARE FEATURES

and select

OK

to

continue.

9. Select the

NETWORKING

tab (Dial-up Connection Properties window).

10. Select

Internet Protocol (TCP/IP)

. Then select

PROPERTIES

to continue.

11. Select

OBTAIN IP ADDRESS AUTOMATICALLY

and select

OK

to continue.

Launch Internet Explorer® version 8.0 or greater to access the Cordex web interface. Type the address

http://10.10.10.203 into the URL section.

9.3.3 CXC Modem Test Feature (via Web interface only)

This feature is a modem dial out test and can only be done using the web interface with Ethernet (Local

or Remote) connection. Refer to the controller setup and computer setup above.

1. Connect the computer modem to a phone jack.
2. Establish connection between controller and computer and launch the CXC user web interface.
3. Once the connection is established, navigate to

Hardware > Test Modem

(Figure 112).

4. Enter the

Telephone Number

.

5. Click

Test Modem

to initiate test.

Figure 140 — Test Modem web interface

Advertising