5.13 Saving Configuration Files

When all changes are made, select

Main Menu > Logs and Files > Manage Configuration File

to save the

configuration file:

Figure 29 — Manage Configuration File – Web Interface

Hard reset

button

Soft reset

button

Figure 30 — CXCU controller

From the controller front panel
The controller front panel has two reset buttons – both are re-

cessed and require a stylus or pen to initiate the reset.
The upper reset button has two modes of operation. When

pressed momentarily, the unit beeps twice and then the micro-

processor resets. The LEDs flash as the CXC performs a selftest

before returning to normal operating mode.
To reset the IP address, press and hold the front panel reset but-

ton for three seconds. The unit will beep three times, reset the IP

address to 10.10.10.201 and disable DHCP. The settings are saved

and the unit resets.

5.12.2 Hard Reset

If the controller is hung up, a hard reset can be initiated by pressing the lower reset button. No files are

saved to flash memory.

5.12 Resetting the CXCU Controller

5.12.1 Soft Reset or Power Down

A soft reset enables the CXC to finish saving files to flash

memory before a power down or restart.

From the main menu
To reset or power down the controller, select

Controller >

Reset

from the main menu and wait for the

Reset Now

pop-up

to appear.

CAUTION!

During reset, the Controller may need to run a defragmentation cycle. Cycling of the LEDs on 

the controller front panel indicate that defragmentation is in progress. A full defragmentation

can take up to 20 minutes to perform. DO NOT POWER DOWN the CXC during this time.