6.5.2 Charge Current Control (CCC)

Use Charge Current Control to limit the battery recharge current to the battery manufacturer’s specified

maximum value. The Battery Properties section (6.5.7) must be completed to enable the Charge Current

Control feature.

Enable

Activiates the Charge Current Control (CCC) feature.

Charge Rate Limit

Amount of current that goes into the battery, which is dependent upon

parameter

Capacity Rating (C)

– see 6.5.7. The Charge Rate amount is

represented in amps (X) or as a C/X value (Capacity Rating/Charge Rate

Amps).
The Charge Rate Amps is recalculated if the Charge Rate C/X value or the

Capacity Rating is modified.

Enable Dynamic CCC

A separate set of Charge Rate Limit values can be input for the Dynamic CCC

feature.

Battery Properties
(LCD only)

The

Battery Properties

button at the bottom of the window links to the Battery

Properties window (see 6.5.7). The return path is to the Charge Current Control

window.

6.5.3 Battery Monitor

The Battery Properties section (6.5.7) must be completed to enable this feature.

Load Type

Select the type of load on the system: constant power, current, or resistive. This

is used for battery capacity calculations.

Disconnect Voltage

The disconnect voltage should be set to the value of the LVD that will

disconnect the battery from the load. The Battery Runtime algorithm uses this

value to calculate the hours remaining during an AC outage.

Reset Battery
Monitor

The Battery Monitor should be reset when installing new or different batteries.

Battery Properties
(LCD only)

The

Battery Properties

button at the bottom of the window links to the Battery

Properties window (see 6.5.7). The return path is to the Battery Monitor

window.

Dynamic CCC Trigger

Use the pull-down menu to select the event that trig-

gers the Dynamic CCC feature (if enabled).

Figure 52 — Charge Current Control – Web