Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 47

Advertising
background image

45

0700015-J0 Rev B

Configuration of DC input Groups
The configuration of the DC input to the inverters provides several different ways to monitor DC input

power and input current.
For bulk monitoring, assign all inverters to DC Input Group 1.
For a system with two or more battery strings, refer to the power system manual for specific configuration

details.

Figure 42 — DC Input Groups

Figure 43 — Set Output (Split Phase System)

6.4.3 Set Output

Set the number of inverters in each phase of your

system. Match the AC input phase to the correspond-

ing AC output phase.

1. Number of Modules:

Enter the total number

of inverter modules that will be installed for that

phase.

2. Redundancy:

Enter the number of inverter

modules that will provide redundant power for

that phase (used to provide system warnings).

3. Phase Shift

: Enter the phase shift for each

output group in your system configuration

1

2

3

Single phase °

0

N/A

N/A

Split phase (120/240 V) °

0

180

N/A

2-pole (120/208) °

0

120

N/A

3-phase (120/208 V) °

0

120

240

4. Nominal Output Voltage

: Enter

120

for all

phases.

5. Press Submit.

CAUTION!

The value entered in the Nominal Output Voltage field can change the actual AC output volt-

age of the inverters. Setting this value to anything other than 120 V will render the UL/CSA 

approval invalid.