6.3.3 Power Save

The Supervisor can improve operational efficiency when conditions warrant by running only the neces-

sary number of rectifiers. The remote shutdown setting (enable or disable) affects correct operation of the

Power Save feature. See also 2.6 for more details.

6.3.3.1 Enable

The Supervisor can control the CXC Power Save feature.

6.3.3.2 Redundant Rectifiers

The Supervisor can specify the number of extra rectifiers to turn on.

6.3.3.3 Max (Maximum) Power Usage

The Supervisor can specify the percentage (of maximum power usage) per rectifier module used in the

computation of the Power Save feature. This works to avoid rectifiers operating continuously at greater

than the set limit (i.e. 95%) and going into current limit frequently due to load surges or power limit condi-

tions; such as, low line voltage or high temperature.

6.3.3.4 Phase Mapping

The user can assign or map a rectifier per input signal for individual phase voltage readings:

Assign/map a rectifier per Phase R, S, and T 

(radio buttons) for the respective signal

Tap Locate and the LEDs of the selected rectifier 

will flash to enable the user to determine the phase 

connection

Discard changes and return to

previous screen

Accept changes and return to

previous screen

Figure 38 — Phase Mapping (rectifiers) window