Table j — controls menu defaults – Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 125

Advertising
background image

123

0700015-J0 Rev B

Table K — Controls menu defaults

Submenu Item

Programmable Range

Default Setting

12Vdc

24Vdc

48Vdc

125Vdc

220Vdc

LVD 1

0-9999999999

10.5V

21.00V

42.00V

101.50V

178.50V

   LVC 1

0-9999999999

12.5V

25.00V

50.00V

120.83V

212.50V

Alarm Priority

Major/Minor/Message

Major

Relay Mapping

1-16 or N/A (mapping disabled)

1

Control

Check = enable LVD control

Checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

LVD 2

0-9999999999

10.5V

21.00V

42.00V

101.50V

178.50V

   LVC 2

0-9999999999

12.5V

25.00V

50.00V

120.83V

212.50V

Alarm Priority

Major/Minor/Message

Major

Relay Mapping

1-16 or N/A (mapping disabled)

2

Control

Check = enable LVD control

Checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

LVD 3

0-9999999999

10.5V

21.00V

42.00V

101.50V

178.50V

   LVC 3

0-9999999999

12.5V

25.00V

50.00V

120.83V

212.50V

Relay Mapping

1-16 or N/A (mapping disabled)

3

Control

Check = enable LVD control

Checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

LVD 4-10

0-9999999999

10.5V

21.00V

42.00V

101.50V

178.50V

   LVC 4-10

0-9999999999

12.5V

25.00V

50.00V

120.83V

212.50V

Alarm Priority

Major/Minor/Message

Major

Relay Mapping

1-16 or N/A (mapping disabled)

N/A

Control

Check = enable LVD control

Not checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

LVD Inhibit (Status)

Active/Inactive

Inactive

Alarm Priority

Major/Minor/Message

Major

Relay Mapping

1-16 or N/A (mapping disabled)

N/A

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

High Volt. Shutdown

0-9999999999

14.25V

29.50V

58.00V

140.17V

246.50V

Alarm Priority

Major/Minor/Message

Major

Relay Mapping

1-16 or N/A (mapping disabled)

N/A

Control

Check = enable LVD control

Not checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

CEMF In-circuit Voltage

0-9999999999

13.70V

27.40V

54.80V

132.43V

232.90V

Bypass Voltage

0-9999999999

13.55V

27.10V

54.20V

130.98V

230.35V

Alarm Priority

Major/Minor/Message

Major

Relay Mapping

1-16 or N/A (mapping disabled)

N/A

Control

Check = enable LVD control

Not checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked