Table R — Inverter Alarm Codes

Alarm Type

Cause

Solution

T2S Event

226

NO TRANSMISSION

Alarm from the T2S - does

not see any TSI- all modules -

system alarm or when the T2S

does not see one of the modules

Replace defective inverter or adapt

configuration

227

DIG INP1 FAILURE

Digital input has changed status

Check device connected on input digital

228

DIG INP2 FAILURE

Digital input has changed status

Check device connected on input digital

229

REDUNDANCY

LOST 

Lost of inverter redundancy

Replace defective inverter or adapt

configuration

230

REDUND + 1 LOST 

Lost of inverter redundancy + 1 

inverter

Replace defective inverter(s) or adapt

configuration

231

SYS SATURATED

Load of system greater than the 

preset value

Reduce load or add inverter on the system, or

change the alarm level trigger.

232

MAIN SOURCE

LOST

Priority source lost (depends

on the configuration AC/AC or 

Online)

1) In AC/AC configuration: Reconnect AC IN or 

check configuration or check live value. 2) In 

Online configuration: Reconnect DC or check 

configuration or check level voltage

233

SEC SOURCE

LOST

Secondary source lost (depends

on the configuration AC/AC or 

Online)

1) In ONLINE configuration: Reconnect AC 

IN or check configuration or check live value. 

2) In AC/AC configuration: Reconnect DC or 

check configuration or check level voltage

234

T2S BUS FAIL    

The communication bus to T2S

has failed

Hardware problem. Replace T2S

235

T2S FAILURE     

T2S has failed

Hard ware problem. Replace T2S

236

T2S STARTED

T2S has started

237

LOG CLEARED     

T2S has cleared the log

238

CONFIG MODIFIED 

Configuration is modified

239

NEW MOD

DETECTED

One more module is plugged

240

DATE & TIME MOD

Date and time are modified

241

CFG READ IN MOD 

T2S has read the CFG

242

LOG NEARLY FULL

This item will be set as, No

alarm, Minor or major alarm. (see

configuration file)

Clear log file

243

T2S FLASH ERROR     

Flash of T2S is corrupt and has

failed

Hardware problem. Replace T2S