71

0700015-J0 Rev B

6.7.1.2 Calibration of Analog Input Channels

Calibrate the selected channel by setting the high point or low point or both as shown in the following

example. For static calibration, refer to the next section.

A more detailed procedure can be found on the Alpha website (www.alpha.ca) under

Technical Documentation > Misc Documents > Method of Procedure

.

Static Calibration
Static calibration enables the Supervisor to calibrate controller analog inputs without the need for a live

signal at the input. This is especially useful for calibrating current inputs for systems in the field. See the

following figures.

Figure 72 — Analog Inputs calibration example (Signals > Calibrate Analog Inputs)

Tap Save or Restore

Default as required

Discard changes and return to

previous screen

Sliders and scroll bars are used for

navigation

Select menu item to configure

Accept changes and return to

previous screen

Figure 73 — Static calibration  – LCD interface