6.6.5.5 Miscellaneous Alarms

Real Time Clock Error

Activates an alarm when any change to the CXC clock occurs due

to a battery failure or the real time clock itself failing. The alarm also

becomes active whenever the date is before Jan. 1, 2000 or after Dec.

31, 2030.

Invalid Device Firmware

Activates an alarm if the firmware of a device (e.g. Cordex rectifier) has

become corrupt and is no longer functioning.

Ground Fault Detected (High
Voltage CXC only)

Activates an alarm when the specified ground fault is detected. The

default value is +/-5 mA.

Improper Controller Shutdown

Sets an alarm if the controller resets unexpectedly.

Invalid Battery Voltage

Activates an alarm when the charging voltage is invalid; e.g., in the

event that the sense leads have become disconnected. The alarm

activates when the charge volts signal drops below 5 V and halts all

control of the system that relies on this signal. If activated (enabled) an

entry is made in the event log.

System Major

The Supervisor can map a relay to the power system major alarm,

which is activated if there are one or more active MAJOR alarms. A

pull-down menu with scroll bars can be used for navigation.

System Minor

The Supervisor can map a relay to the power system minor alarm,

which is activated if there are one or more active MINOR alarms. A

pull-down menu with scroll bars can be used for navigation.

Tap Configure to edit 

selected menu item

Select menu item to configure

Accept changes and return to

previous screen

Figure 66 — Miscellaneous Alarms Categories – LCD