Conv. Major Fail Count
This menu item enables the Supervisor to set the total number of converter fail alarms that will trigger

the CXC converter major alarm. The activation value must be greater than or equal to the total number

entered for the minor converter fail count alarm.

Conv. Minor Fail Count
This menu item enables the Supervisor to set the total number of converter fail alarms that will trigger the

CXC converter minor alarm. The activation value must be less than or equal to the number entered for the

major converter fail count alarm.

Conv. Out of Tolerance
This menu item enables the Supervisor to set an alarm condition when a converter out of tolerance is

detected. The activation value is factory set.

Conv. Comms Lost
This menu item enables the Supervisor to set an alarm condition when converter communications is lost.

The activation value is factory set.

Conv. Input Voltage Fail
This menu item enables the Supervisor to set an alarm condition when a converter input voltage fail is

detected. The activation value is factory set.
The activation value for Input Voltage Fail detection is determined to be when the number of converters in

Input Voltage Fail divided by the number of converters acquired is greater than or equal to 90%.

Conv. Fan Fail
The purpose of this feature is to enable the CXC to trigger the alarm when a fan fail (speed error or failed

fan) condition has occurred in any of the converters in the system.
The Fan Fail Alarm is true when the CXC receives a Fan Fail or Fan Speed Error alarm from any convert-

er.
The Fan Fail Alarm is cleared when all Fan Fail and Fan Speed Error alarms are cleared from all the con-

verters.
Each time that the Fan Fail Alarm goes on/off, the “event” is logged in the Event History. Since it is a con-

verter alarm, up to nine converters (up to 27 fan fail alarms) that are in alarm will be logged. If more than

nine converters are in alarm an additional entry will be made indicating the total number of converters in

alarm.
The activation value is factory set.

Conv. Load Current High
This menu item enables the Supervisor to program the setting for the converter load amps alarm. When

the current to the load has exceeded this setting, an alarm is activated and the message CONV. LOAD

CURRENT HIGH is displayed on the GUI.

Conv. Low Output Voltage
When the converter’s output voltage falls below the Supervisor-specified value, the alarm is activated and

the message CONV. LOW OUTPUT VOLTAGE is displayed on the GUI.

Conv. High Output Voltage
When the converter’s output voltage exceeds the Supervisor-specified value, the alarm is activated and

the message CONV. HIGH OUTPUT VOLTAGE is displayed on the GUI.