Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 84

Advertising
background image

0700015-J0 Rev B

82

Start Trigger

– enables data collection to be started manually, by event or by time. For example, select

Customize to edit/build an equation from the list of operands (alarms and signals) and operators (arith-

metic and logic):

Figure 91 — Alarm Equation web interface window

Figure 92 — Log Frequency

Mathematical operators
+

Add

-

Subtract

*

Multiply

/

Divide

Logical operators:
&

AND

|

OR

!

NOT TRUE

=

EQUAL TO, compare for equality

<

LESS THAN

>

GREATER THAN

(

OPEN PARENTHESIS, used with

a close parenthesis to set apart

arguments to a mathematical

function

)

 CLOSE PARENTHESIS, see 

open parenthesis; used to clarify

the order of operations

Definitions
Data Log Files

– this list shows the filename (up to 16) and the number of records associated with each.

Select the filename to display and edit the information in the adjacent window.
File Information

– description and status of the log file is shown here.

Log Records

is the number of records to be saved in the log file. Click on the value to edit.

Log Limit

changes depending on the number of signals selected and the number of records in the other

log files.

NOTE:

Recommended size is up to seven signals and a maximum one thousand entries, as very large log files 

may not be viewable. If the datalog screen comes up blank, the log is too large to be displayed.

File Save Option

enables a FIFO (first in first out) or “Stop when full” means of data collection.

Log Signals

allows selection of log signals from a list (max. 32) See Figure 89.

Log Frequency

– determines how often the data is collected. The default time interval is 60 seconds

and the range is from ten to 86,400 seconds (24 hours). An interval may also be set based upon when a

selected signal changes by the Delta Level; click on the value to edit.