Factory ranges and defaults, Table f — rectifiers menu defaults, Table g — converters menu defaults – Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 122

Advertising
background image

0700015-J0 Rev B

120

11. Factory Ranges and Defaults

Table G — Rectifiers menu defaults

Submenu Item

Programmable

Range

Default Setting

12Vdc

24Vdc

48Vdc

125Vdc

220Vdc

Float (FL) Voltage

0-9999999999

13.50V

27.00V

54.00V

130.50V

229.5V

Equalize (EQ) Voltage

0-9999999999

13.75V

27.50V

55.00V

132.92V

233.75V

Battery Test (BT) Voltage

0-9999999999

11.50V

22.00V

44.00V

106.33V

187.00V

OVP

0-9999999999

14.25V

29.00V

57.00V

137.75V

242.25V

LVA

0-9999999999

11.00V

22.00V

44.00V

106.33V

187.00V

HVA

0-9999999999

14.00V

28.00V

55.50V

134.13V

235.88V

Current Limit (CL)

0-9999999999

100%

Power Limit (PL)

0-9999999999

100%

Equalize Timeout

0-9999999999

30 hours

Battery Test Duration

0-9999999999

8.0 hours

Slope (Adjust)

0-9999999999

1.00%

Backlight Timeout

0-32767

1 minute

Security Code

0-32767

123

Module Start Delay

0-32767

1 second

System Start Delay

0-32767

0 seconds

Soft Start Ramp Rate

Normal/Fast

Normal

Temp Display Scale

Celsius/Fahrenheit

Celsius

Current/Power Limit Alarm

Enable/Disable

Disable

Remote Shutdown

Enable/Disable

Enable

Local Access Alarm

Enable/Disable

Enable

Ramp Test

Enable/Disable

Enable

Power Save

Enable/Disable

Disable

Redundant Rectifiers

0-32767

1

Maximum Power Usage

0-32767

80%

Table H — Converters menu defaults

Submenu Item

Programmable Range

24V–48V Defaults

48V–24V Defaults

Output Voltage

0-9999999999

54.00V

27.00V

OVP

0-9999999999

57.00V

28.50V

Input Voltage Shutdown

0-9999999999

21.0V

42.0V

Input Voltage Restart

0-9999999999

25.0V

50.0V

Start Delay

0-32767

1 second

Current Limit (CL) Alarm

Enable/Disable

Enable