7 signals, Table d — analog input channel assignments, 1 calibrate analog inputs – Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 72: 1 overview of analog input channels

Advertising
background image

0700015-J0 Rev B

70

6.7 Signals

This menu category consists of system identifiers and calibration controls. Parameters can be set/ac-

cessed such as controller signals, rectifier signals, analog and digital inputs. With the web interface, data

logging can be configured.

6.7.1 Calibrate Analog Inputs

This menu item provides a direct link to the Analog Inputs menu heading; which may also be accessed

via the menu item Configure Signals, see 6.7.2.

6.7.1.1 Overview of Analog Input Channels

The majority of the CXC analog input channels are each designed to accept a specific input signal.
2.1 summarizes the analog input channel assignments; which may vary depending on the hardware con-

figuration (list options):

=

Installed

BiV

=

-60 V to +60 V

I

=

-50 mV to +50 mV

T

=

-55ºC to +100ºC (powered)

V

=

0 to 60 V

X

=

Not Installed

Table E — Analog input channel assignments

Channel

List Option

CXCU

Assignment

120

121

122

123

124 125

129

V1

X

V2

X

GP1

T1

T1

T1

T1

V3

T1

T1

T1

GP2

T2

T2

T2

T2

V4

T2

T2

T2

GP3

X

T3

X

T3

V5

BiV

T3

X

GP4

BiV

T4

BiV

T4

T1

BiV

T4

X

I1

I2

X

X

X

X

X

I3

X

X

X

X

X

X

I4

X

X

X

X

X

X