CP-72 CHARACTER FORMAT

The MLP-Drive uses three different character formats. Enter the number for the
required format, as listed below.

1 = 8 Data Bits, No Parity, One Stop Bit
2 = 7 Data Bits, Even Parity, One Stop Bit
3 = 8 Data Bits, No Parity, Two Stop Bits

CP-73 CONTROL MASK

The Serial Communications can control some of the digital input functions. Enter the
number for the required functions, as listed below.

0 = F–Stop only
1 = F–Stop, Run, R–Stop
2 = F–Stop, Master/Follower, Setpoint Select
3 = All of the Above

MP-58 SERIAL COMMUNICATIONS ERROR

Serial Communications Error identifies errors in the last transmitted message that was
sent to the MLP-Drive by the host computer. The mode that displays a number “1”
indicates the error. In the example below, “Invalid Parameter Code” is the error.

Structure Error (Parity,Framing,No ETX, No STX)

Invalid Parameter Code

Invalid Parameter Data or Out of Data Min-Max Range

Control Mask Error

Code