Control command send, Character 1 - stx, Characters 2, 3 - device – CONTREX MLP-Drive User Manual

Page 120: Character 4 - message type

Advertising
background image

3 - 82

Control Command Send

The Control Command Send allows the host computer to control the operating
functions of the MLP-Drive that are associated with the digital inputs (Run, Stop,
Setpoint Select and Master/Follower).

Table 3-53 Control Command Send - Host Transmission

Character #

1

2

3

4

5

6

7

8

9

10

11

12

DEV # DEV # MSG

PAR # PAR #

DATA DATA

DATA

DATA

DATA

DESC

STX

10s

1s

TYPE

10s

1s

1000s 100s

10s

1s

FORM

ETX

ASCII

STX

0-9

0-9

1

0

0

0

0

0-1

0-9

0

ETX

The following is a description of the Control Command Send - Host Transmission.

Character 1 - STX:

This is the first character in the character string. None of the other characters will
be recognized without this character prefix. Always use the ASCII “STX” character;
it enables the MLP-Drives receive buffer.

Characters 2, 3 - Device #:

These characters are the access address of the MLP-Drive. This number identifies
individual MLP-Drives on a mutltidrop system. The MLP-Drive will accept data only
if this number matches the ML-Drive's address (CP-70), with the exception of a “00”
address. The “00” address is universally accepted by all MLP-Drives that are on
the RS485 Serial Communications Interface.

Character 4 - Message Type:

This character should always be “1”.