Mounting, Mounting -3 – CONTREX MLP-Drive User Manual

Page 19

Advertising
background image

2 - 3

MOUNTING

This section contains instructions for mounting the MLP–Drive in the door panel of a
NEMA Industrial Electrical enclosure. The MLP–Drive is packaged in a compact 1/4
DIN Vertical Instrument Enclosure that mounts easily in the door of your Industrial
Electrical Enclosure. The Electrical Enclosure must have an IP54 rating or higher to
comply with CE installations.

To mount the MLP–Drive:

1) The NEMA Industrial Electrical Enclosure that will house the MLP–Drive must

conform to the following environmental conditions:

Temperature: 0 - 55 degrees C

(Internal NEMA enclosure temperature)

Humidity: 0 - 95% RH non-condensing

Environment: Pollution degree 2 macro - environment

Altitude: To 3300 feet (1000 meters)

NOTE: Allow adequate spacing between the MLP–Drive and other equip-
ment to provide for proper heat convection. Placing the MLP–Drive too
close to adjacent equipment could cause the interior ambient temperature to
exceed 55 degrees C. Spacing requirements depend on air flow, enclosure
construction and applied horsepower.

2) The dimensions for the door panel cutout are 3.65"+ .03" x 3.65 +.03"

(see Figure 2-1). Allow two inches of clearance on all sides of the cutout for
mounting clamp attachments, wire routing and heat convection.

3) Insert the MLP–Drive through the door panel cutout until the gasket and bezel

are flush with the door panel (see Figure 2-1).

4) Slide the mounting clamps into the slots that are located on the top and

bottom of the MLP–Drive. Tighten the mounting screws until the MLP–Drive
is mounted securely in the NEMA Electrical Enclosure. Do not overtighten.