Figure 4-2 motor does not run flowchart – CONTREX MLP-Drive User Manual

Page 143

Advertising
background image

4 - 13

MP-50 =

0010(Master)

MP-50 =

0100(Follower)

MP-50 =

0001(Direct)

Yes

Motor Does Not Run

Problem

Corrected

Yes

Yes

No

No

No

No

Setpoint

is correct ?

No

Yes

MP-45 is

Correct ?

Enter Correct

Setpoint

No

Yes

MP-46 is

Correct ?

Enter Correct

Scaling

No

Yes

MP-47 is

Zero ?

Check

Wiring

CP-06

is correct ?

Yes

No

No

Yes

MP-53 =

1000 (F–Stop)

MP-53 =

0100 (R–Stop)

MP-53 =

0010 (Run)

MP-53 =

0001 (Jog)

No

Yes

Yes

No

No

No

No

No

J5, Pin 7 is

shorted

to common

J5, Pin 6 is

shorted

to common

Yes

Short J5,

Pin 7

to common

Problem

Corrected

No

Consult Tech

Support

Yes

Yes

No

Yes

CP-05

is correct ?

Yes

No

Enter Correct

Jog Setpoint

Short J5,

Pin 6

to common

No

No

Consult Tech

Support

1-800-342-4411

Figure 4-2 Motor Does Not Run Flowchart