Alarms, Alarms -52 – CONTREX MLP-Drive User Manual

Page 90

Advertising
background image

3 - 52

Alarms

The Control Parameters for Alarms are identical for both the Master and the Follower
modes of operations. By entering values in the Control Parameters for the Alarms
(CP-12, CP-13, CP-14, CP-15), you can establish circumstances under which the
MLP–Drive will alert you to potential operating problems. The Alarm 1 Format (CP-10)
and Alarm 2 Format (CP-11) can be set to activate at any combination of low speed,
high speed, ramped error or scaled error conditions. Alarm 1 Format is used to control
Dig_Out1 (J5 pins 15, 17). Alarm 2 Format is used to control Dig_Out2 (J5 pins 16, 17).
The alarm outputs can be wired to activate a warning light, a warning sound, or to shut
down the system under specified conditions.

The MLP–Drive comes factory pre-loaded with default Control Parameters for Alarms.
These default parameter values are set for widely generic conditions that generally will
not activate the alarm. This allows you to either operate your system unfettered by the
alarm or design your own alarm conditions that are unique to your system. The factory
default Control Parameters for the Alarms are found in Table 3-43. To modify these
default parameters, refer to Table 3-44.

Table 3-43 Default Alarms Control Parameters

CP

Parameter Name

Parameter Value

CP-10

Alarm 1 Format

15

CP-11

Alarm 2 Format

15

CP-12

Low Alarm

0

CP-13

High Alarm

2000

CP-14

Ramped Error Alarm

2000

CP-15

Scaled Error Alarm

2000