Input test #4 - to test the logic inputs – CONTREX MLP-Drive User Manual

Page 137

Advertising
background image

4 - 7

Input Test #4 - To Test the Logic Inputs

Press the “UP” or “DOWN” scroll keys until the diagnostic indicator and
the number “4” are visible on the left side of the LED display.

Press “Enter” to start the test.

The LED display will be blank unless an input has been shorted. If an
input has been shorted, it's number will display. For example, if the
number three appears in the display, then R–Stop has been shorted.
To test an input, short that input and open all of the other inputs.

Input Closure

Display

RUN (J5-4)

1

JOG (J5-5)

2

R–STOP (J5-6)

3

F–STOP (J5-7)

4

MASTER/FOLLOWER (J5-9)

5

SETPOINT SELECT (J5-10)

6

SCROLL UP (J5-11)

7

SCROLL DOWN (J5-12)

8

Press CLEAR to exit the test.
Press “CODE SELECT” only if you want to exit diagnostics.