Master Mode Example

The following example demonstrates how scaling and setpoint Control Parameters are
entered for a typical Master mode of operation:

A pump delivers 15 gallons/minute when the motor runs at a maximum
RPM of 1725. The motor shaft is equipped with a 30 tooth Ring kit.
The Master Engineering Units are gallons per minute. Master Setpoint
1 will be setup to pump 10 gallons per minute when it is the active
setpoint. Master Setpoint 2 will be setup to pump 5 gallons per minute
when it is the active setpoint.

Table 3-7 shows the scaling Control Parameters that would be entered in the
MLP–Drive for this example.

Table 3-7 Master Mode Control Parameters Example

CP

Parameter Name

Parameter Value

CP-34

Max RPM Feedback

1725

CP-31

PPR Feedback

30

CP-20

Master Engineering Units

15.0

CP-01

Master Setpoint 1

10.0

CP-02

Master Setpoint 2

5.0

After the Scaling and the Master Setpoints for your system have been entered, you can
enter the Acceleration/Deceleration Control Parameters for the Master mode. The
Acceleration/Deceleration Control Parameters are identical for both the Master and the
Follower modes of operations. Acceleration/Deceleration is discussed in

Operation:

Control Parameters, Acceleration/Deceleration.