Follower Mode - Analog Lead

The MLP-Drive can be scaled for Engineering Unit setpoint entry and Tach display
operation using the analog input for the lead signal. The following Control Parameters
give the MLP-Drive the necessary information for analog lead operation in Follower
mode.

Analog Input Allocation(CP-84)

Setting CP-84, Analog Input Allocation, to a value of "1" allocates the
analog input to be used as the lead source.

Follower Engineering Units (CP-21)

The actual value of the Follower Engineering Units if the system were to
operate with an analog lead level of 10.0 volts and a feedback of Max
RPM Feedback (CP-34). This is the maximum calibrated analog input
level (refer to Installation/Setup: Calibration, Analog Input Calibration).

Note: The analog input does not need to operate to 10.0 volts full scale to be

used for analog lead.

Max RPM Feedback (CP-34)

This is the maximum RPM of the feedback sensor shaft during system
operation.

PPR Feedback (CP-31)

The number of gear teeth or encoder lines on the follower feedback
sensor per revolution.

Table 3-19 Default Scaling Control Parameters

CP

Parameter Name

Parameter Value

CP-84

Analog Input Allocation

0

CP-21

Follower Engineering Units

1.000

CP-34

Max RPM Feedback

2000

CP-31

PPR Feedback

60