Follower Mode Examples A and B

Example A demonstrates how scaling and setpoint Control Parameters are entered for
a typical Follower mode of operation that uses a ratio setpoint:

The Lead pump delivers 10 gallons/minute when the motor is running at
a maximum RPM of 1725. The Lead sensor shaft is equipped with a 60
tooth Ring kit. The Follower pump delivers 30 gallons/minute when the
motor is running at a maximum RPM of 1800. The Follower sensor
shaft is equipped with a 30 tooth Ring kit. Follower Setpoint 1 will be
set so that when the Lead pump delivers 5 gallons/minute, the Follower
pump will deliver 15 gallons/minute. Follower Setpoint 2 will be set so
that when the Lead pump delivers 5 gallons/minute, the Follower pump
will deliver 22.5 gallons/minute.

Table 3-17 shows the Control Parameters that would be entered in the MLP–Drive for
Example A.

To find the ratio for the Follower Engineering Units (CP-21) for Example A:

Follower E.U. at Max Follower RPM

30

Follower E.U. (CP-21) =

_____________________________________________________

=

___

=

3

Lead E.U. at Max Lead RPM

10

30 gal / min

The Follower Engineering Units when the Follower is operating
at the maximum RPM.

Divided by

10 gal / min

The Lead Engineering Units when the Lead is
operating at maximum RPM.

Equals

3.00

Follower Engineering Units (CP-21) as a ratio of Follower to
Lead.