CONTREX MLP-Drive User Manual

Page 180

Advertising
background image

C - 14

CP-69

TRIM AUTHORITY

Trim Authority determines how much influence the PID term has on the control output. If stability
cannot be obtained through the standard tuning procedure, reduce CP-69 until stable tuning is
achieved.

CP-70

DEVICE ADDRESS

Device Address (CP-70) is the physical address of the MLP–Drive, which can be set from 1 to
32. Each individual MLP–Drive on a multidrop RS485 communications link needs a unique
Device Address. The address “00” will be globally accepted by all of the MLP–Drives on a
communications link, however, they will not send a response message back to the host computer
when this global address is used.

CP-71

BAUD RATE

There are six different baud rates (data rates) for the MLP–Drive. Enter the number for the
required function in Baud Rate (CP-71), as listed below.

1 = 300 Baud
2 = 600 Baud
3 = 1200 Baud
4 = 2400 Baud
5 = 4800 Baud
6 = 9600 Baud

CP-72

CHARACTER FORMAT

The MLP–Drive uses three different character formats. Enter the number for the required format
in Character Format (CP-72), as listed below.

1 = 8 Data Bits, No Parity, One Stop Bit
2 = 7 Data Bits, Even Parity, One Stop Bit
3 = 8 Data Bits, No Parity, Two Stop Bit