Wiring, Wiring -5, Warning – CONTREX MLP-Drive User Manual

Page 21

Advertising
background image

WIRING

WARNING

Can cause severe injury, death, or damage
to equipment.

Hazardous voltages!

The MLP-Drive should only be installed by
a qualified electrician.

This section contains the power supply, input, and output wiring for the MLP-Drive.

Please read this section prior to wiring the MLP-Drive to ensure that you make the

appropriate wiring decisions.

NOTE:

The installation of this motor control must conform to area and local electrical

codes. For information, refer to the National Electrical Code (NEC) Article 430

published by the National Fire Protection Association, or the Canadian Electrical

Code (CEC). Refer to local codes as applicable.
Branch Circuit Protection: “Suitable For Use On A Circuit Capable Of Delivering

Not More Than 5,000 rms Symmetrical Amperes, 250 Volt Maximum.”

Class G branch circuit fuses rated 250V, 15A shall be provided in the end

application.
Motor overload protection shall be provided in the end installation in accordance

with the NEC.

This drive does not provide over-temperature sensing.
Use a minimum wire gauge of 18 AWG.
Use shielded cable to minimize equipment malfunctions from electrical noise.
Keep the AC power wiring (J3) physically separated from all other wiring on the

MLP-Drive. Failure to do so could result in additional electrical noise and cause

the MLP-Drive to malfunction.
A hand operated supply disconnect device must be installed in the final

application. The primary disconnect device must meet EN requirements.
Inductive coils on relays, contactors, solenoids that are on the same AC power

line or housed in the same enclosure should be suppressed with an RC network

across the coil. For best results, use resistance (r) values of 50 ohms and

capacitance (c) values of 0.1 microfarads.
Install an AC line filter or isolation transformer to reduce excessive EMI noise,

such as line notches or spikes, on the AC power line.

2 - 5

Advertising