Using static parameters with timers, Figure 91, Setup view: static parameters tab – Vaisala Hydromet Data Collection Platform User Manual

Page 189

Advertising
background image

Chapter 5 ________________________________________ Advanced Use of Lizard Setup Software

VAISALA______________________________________________________________________ 187

Using Static Parameters with
Timers

It is often necessary to change the interval or synchronization time of
timers. You can define these to be read from static parameters. Static
parameters can also be changed at runtime by using the spset command.

First, it is recommended that you create the parameters to be used in the
Static Parameters tab of the Setup view.

0711-106

Figure 91

Setup View: Static Parameters Tab

To change an interval or synchronization, proceed as follows:

1.

Go to the Timers view.

2.

Right-click the timer to be modified either in the Interval or the
Synch time column. Select Advanced edit from the list. The Edit
Timer
window opens; see

Figure 92 on page 188

.

NOTE

The Measure field has to be changed to seconds. In order to change it,
double-click the measure field of the static parameter in question and
select second.