SECTION 6 - JLG CONTROL SYSTEM (S/N 61718 TO PRESENT)

6-38

– JLG Lift –

3120895

8/4

Flash code 8/4 indicates problems with the envelope system. Only occur
on machines with envelope control.

10

BOOM ANGLE SENSOR DISAGREE-
MENT

The boom angle sensors are reporting angles that differ too greatly. An EMS
cycle is required.

BOOM LENGTH SWITCH FAILED

The boom length switch inputs are reporting the same state. An EMS cycle is
required.

BOOM LENGTH SWITCH/SENSOR
DISAGREEMENT

The boom length switch and sensor differ in their reports of extended or
retracted. An EMS cycle is required.

BOOM LENGTH SENSOR NOT
DETECTING LENGTH CHANGE

The boom length sensor has not detected a change in length while the user is
commanding telescope. An EMS cycle is required.

BOOM LENGTH SENSOR OUT OF
RANGE HIGH

Indicates that the voltage for the boom length sensor is above the expected
range.

BOOM LENGTH SENSOR OUT OF
RANGE LOW

Indicates that the voltage for the boom length sensor is below the expected
range.

BOOM LENGTH SENSOR VALUE OUT
OF RANGE HIGH

Indicates the length reported for the boom length sensor is above the expected
range. An EMS cycle is required.

BOOM LENGTH SENSOR VALUE OUT
OF RANGE LOW

Indicates the length reported for the boom length sensor is below the expected
range. An EMS cycle is required.

BOOM ANGLE SENSOR #1 COMMU-
NICATIONS FAULT

Boom angle sensor #1 lost communications with the BLAM. An EMS cycle is
required.

BOOM ANGLE SENSOR #2 COMMU-
NICATIONS FAULT

Boom angle sensor #2 lost communications with the BLAM. An EMS cycle is
required.

ANGLE SENSOR #1 INVALID ANGLE

An EMS cycle is required.

ANGLE SENSOR #2 INVALID ANGLE

An EMS cycle is required.

WRONG TELE RESPONSE

The boom telescope is contrary to the user command

WRONG LIFT RESPONSE

The boom lift is contrary to the user command

TOWER ANGLE SENSOR DISAGREE-
MENT

The tower angle sensors are reporting angles that differ too greatly. An EMS
cycle is required.

TOWER LENGTH SENSOR DIS-
AGREEMENT

The tower length sensors are reporting angles that differ too greatly. An EMS
cycle is required.

MAIN ANGLE SENSOR DISAGREE-
MENT

The main boom angle sensors are reporting angles that differ too greatly. An
EMS cycle is required.

BOOM LENGTH SENSOR #1 OUT OF
RANGE HIGH

Reported from the BLAM, indicates tower length sensor one value is out of
range high.

BOOM LENGTH SENSOR #1 OUT OF
RANGE LOW

Reported from the BLAM, indicates tower length sensor one value is out of
range low.

BOOM LENGTH SENSOR #2 OUT OF
RANGE HIGH

Reported from the BLAM, indicates tower length sensor two value is out of
range high.

BOOM LENGTH SENSOR #2 OUT OF
RANGE LOW

Reported from the BLAM, indicates tower length sensor two value is out of
range low.

TWR LENGTH SENSOR NOT
DETECTING LENGTH CHANGE

Tower tele is being commanded and the length sensors are not changing
value.

TWR LENGTH MOVEMENT WITHOUT
CMD

Tower length is changing without a tower tele command

TWR LENGTH SENSOR ONE VALUE
OUT OF RANGE HIGH

This fault is reported by the Ground module when the length sensor value is
outside the constant data limit

Table 6-3. Help Fault Codes, Displayed Faults, and Descriptions - S/N 66995 to Present

Fault Flash

Code

Communicated (Displayed on

Analyzer) Fault

Description

Priority