Automatic switches, Switch wiring - low side, high side – JLG 460SJ Service Manual User Manual

Page 406

Advertising
background image

SECTION 7 - BASIC ELECTRICAL INFORMATION & SCHEMATICS

7-4

– JLG Lift –

3120895

Automatic Switches

If the switch is actuated automatically, by temperature or
pressure for example, find a way to manually actuate the
switch to test it. Do this either by applying heat or pres-
sure, for example, to the switch. These switches may need
to be energized to actuate.

1. Connect instrumentation to monitor and/or control

the parameter the switch is measuring.

2. Observe switch state in control system with the Ana-

lyzer. See vehicle or control system documentation
on how to do this.

3. Operate system such that the switch actuates. This

could be going over a certain pressure or tempera-
ture, for example. The state indicated in the control
system should change.

Switch Wiring - Low Side, High Side

When controlling a load, a switch can be wired between
the positive side of the power source and the load. This
switch is called a "high side" switch. The switch supplies
the power to the load. When a switch is wired between the
negative side of the power source and the load, it is a "low
side" switch. The switch provides the ground to the load.

A low side switch will allow voltage to be present on the
load. No power is applied because the switch is stopping
current flow. This voltage can be seen if the measurement
is taken with one test lead on the load and the other on
the battery negative side or grounded to the vehicle. What
is actually being measured is the voltage drop across the
switch. This could mislead a technician into thinking the
load is receiving power but not operating. To produce an
accurate picture of power or voltage applied to the load,
measure voltage across the load’s power terminals. Also,
the technician can measure the voltage at both power ter-
minals with respect to battery ground. The difference
between those two measurements is the voltage applied
to the load.

7.4 APPLYING SILICONE DIELECTRIC

COMPOUND TO ELECTRICAL
CONNECTIONS

NOTE: This section is not applicable for battery terminals.

JLG P/N 0100048 DIELECTRIC GREASE (NOVAGARD G661) IS
THE ONLY MATERIAL APPROVED FOR USE AS A DIELECTRIC
GREASE.

NOTE: Do NOT apply dielectric grease to the following con-

nections:

• Main Boom Rotary sensor connections (on Celesco

Sensor),

• LSS Modules connections,

• Deutz EMR 2 ECM connection.

Silicone Dielectric Compound must be used on all electri-
cal connections except for those mentioned above for the
following reasons:

• To prevent oxidation at the mechanical joint between

male and female pins.

• To prevent electrical malfunction caused by low level

conductivity between pins when wet.

Use the following procedure to apply Silicone Dielectric
Compound to the electrical connectors. This procedure
applies to all plug connections not enclosed in a box. Sili-
cone grease should not be applied to connectors with
external seals.

1. To prevent oxidation, silicone grease must be

packed completely around male and female pins on
the inside of the connector prior to assembly. This is
most easily achieved by using a syringe.

NOTE: Over a period of time, oxidation increases electrical

resistance at the connection, eventually causing cir-
cuit failure.

2. To prevent shorting, silicone grease must be packed

around each wire where they enter the outside of the
connector housing. Also, silicone grease must be
applied at the joint where the male and female con-
nectors come together. Any other joints (around
strain reliefs, etc.) where water could enter the con-
nector should also be sealed.

NOTE: This condition is especially common when machines

are pressure washed since the washing solution is
much more conductive than water.