Gold Solo Trombone Installation Guide

Installation

MAN-G-SOLTROIG (Ver. 1.3)

www.elmomc.com

49

4.7.2.1.b Single-Phase Direct-to-Mains Connection Topology

Figure 11: Non-Isolated Single-Phase Connection Topology

The Power Supply is connected directly to the mains AC line.

Warning

:

Do not connect VN- to PE. In a direct-to-mains connection the VN- must not be

connected to the PE, as this will cause irreparable damage to the system.

• Take care and note that in a direct-to-mains connection the Neutral point is not the most

negative voltage level. It is the mid-point level of the rectified DC bus.