Serial communications, Chapter, Overview – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 110: Logic control data, Control wiring

Advertising
background image

Chapter

8

Serial Communications

Overview

The SMC Dialog Plus controller can be started and stopped through
programmable logic controllers using an optional communication
module. Additionally, parameter data can be read to the logic
controller through data transfer. The amount of information that can
be transferred from the SMC Dialog Plus controller is determined by
the DIP switch settings on the communication module.

Note: Parameter values modified while the motor is operating are

not valid until the next start sequence begins.

Logic Control Data

The information in Table 8.A provides the logic control information
that can be sent to the SMC Dialog Plus controller through the logic
controller’s output image table.

Table 8.A Logic Control Data

Only one bit may be asserted at any given time.

The stop bit will take priority in operation when more than one bit is asserted. Other bits will be ignored until the stop bit is reset.

A 0 to 1 transition is required for a valid command.

Assert the Option Command bit to initiate an option maneuver such as Pump Stop.

Control Wiring

Refer to Figure 3.14 on page 3-10 for the applicable wiring diagram
to achieve start-stop control via the SCANport.

Logic Bits

Description

Definition

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Stop

1 = Stop
0 = Not Stopped

X

Start

1 = Start
0 = Not Start

X

Option

Command

1 = Option Init.
0 = Not Option Init.

X

Clear Faults

1 = Clear Faults
0 = Not Clear Faults

Bits 4–15 are not used