Specifications

Assumes the Bulletin 825 converter module is utilized.

The SMC Dialog Plus controller calculates the current values to two decimal place resolution while
displaying only to tenths of Amps. The display accuracy provided is, therefore, reduced by the
truncation. The affect of truncation on accuracy will be dependent on the magnitude of the value.

Assumes a balanced supply.

Other Ratings

UL/CSA/NEMA

IEC

EMC Emission Levels

Conducted Radio Frequency
Emissions

Class A

Radiated Emissions

Class A

EMC Immunity Levels

Electrostatic Discharge

8kV Air Discharge

Radio Frequency Electromagnetic
Field

Per IEC 947-4-2

Fast Transient

Per IEC 947-4-2

Surge Transient

Per IEC 947-4-2

Overload Characteristics:

Type

Solid-state thermal overload with phase loss

Current Range

1.0–999.9 Amps

Trip Classes

10, 15, 20, and 30

Trip Current Rating

120% of Motor FLC

Number of Poles

3

Metering Accuracy

Voltage

± 2%

Current

± 5%

① ②

kW

± 10%

kWH

± 10%

Displacement Power Factor

± 3%

Converter Module Output

Cat. No.:

825-MCM20
825-MCM180
825-MCM630

78.8 mV/A
9.85 mV/A

1.231 mV/A