Terminal locations (cont.), Control power, Control voltage – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 50: Control wiring

Advertising
background image

3-4

Wiring

Terminal Locations (cont.)

Table 3.C Lug Wire Capacity and Tightening Torque

Control Power

Control Voltage

Depending upon the catalog number ordered, the SMC Dialog Plus
controller will accept a control power input of:

100

240V AC, (–15/+10%), 1 phase, 50/60 Hz

24V AC, (–15/+10%), 1 phase, 50/60 Hz

24V DC, (–20/+10%), 1 phase

Refer to the product nameplate.

Connect control power to the controller at terminals 11 and 12. The
control power requirement for the control module is 40 VA. For
controllers rated 97A

1000A, control power is also required for the

heatsink fans as defined in Table 3.D. Depending on the specific
application, additional control circuit transformer VA capacity may
be required.

Table 3.D Heatsink Fan Control Power

Control Wiring

Table 3.E provides the control terminal wire capacity and the
tightening torque requirements. Each control terminal will accept a
maximum of two wires.

Table 3.E

Control Wiring and Tightening Torque

SMC

Rating

Lug Kit

Cat. No.

Conductor

Range

Max. No.

Lugs/Pole

Tightening Torque

Line
Side

Load

Side

Wire –

Lug

Lug –

Busbar

97–

135A

199-LF1

16–120 mm

2

(#6–4/0 AWG)

3

3

31 N-m

(275 lb-in)

31 N-m

(275 lb-in)

180–
360A

199-LF1

16–120 mm

2

(#6–4/0 AWG)

6

6

31 N-m

(275 lb-in)

31 N-m

(275 lb-in)

500A

199-LG1

25–240 mm

2

(#4–500 AWG)

6

6

42 N-m

(375 lb-in)

45 N-m

(400 lb-in)

650–
720A

199-LG1

50–240 mm

2

(1/0–500 AWG)

9

9

42 N-m

(375 lb-in)

45 N-m

(400 lb-in)

850–

1000A

199-LJ1

50–240 mm

2

[(2) 1/0–500 AWG]

6

6

42 N-m

(375 lb-in)

45 N-m

(400 lb-in)

SMC Rating

Heatsink Fan VA

97–360A

45

500A

145

650–1000A

320

Wire Size

Torque

0.75–2.5 mm

2

(#18–#14)

.8 N-m (7 lb-in.)