Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 163

Advertising
background image

10-14

Troubleshooting

Power Module and Interface
Board Resistance Check (cont.)

2.

Measure resistance between:

pins J14 and J15 for phase L1/T1

pins J9 and J10 for phase L2/T2

pins J1 and J2 for phase L3/T3

The resistance should be approximately 100

.

If any of the resistances measure greater than 100

, recheck the

resistance values directly at the gate lead connectors as shown in
Figure 10.9.

Based on the results, one of the following actions will be required:

1.

All resistance values are valid - Replace interface board.

2.

Resistance(s) measure greater than 100

– Replace correspond-

ing power pole(s).

Thermistor Resistance

1.

Measure resistance between:

pins J6 and J24 for phase L1/T1

pins J8 and J23 for phase L2/T2

pins J7 and J22 for phase L3/T3

The resistance should be less than 500

.

If any of the resistances measure greater than 500

, recheck the

resistance values directly at the thermistor lead connectors as shown
in Figure 10.9.

Based on the results, one of the following actions will be required:

If all resistance values are valid, replace interface board.

If resistance(s) measure greater than 500

, replace the

corresponding power pole(s).

Figure 10.9 Gate and Thermistor Lead Identification (180–1000A)