Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 172

Advertising
background image

Parameter Information

B-3

Table B.1 (cont.) Parameter List

Group

Parameter

Description

Parameter

Number

Display

Units

Scale

Factor

Minimum

Maximum

Default
Setting

User

Setting

Basic Setup

(cont.)

Slow Speed with Braking

Slow Speed

Select

44

Low, High

High

Slow Accel

Current

46

% FLC

1

0

450

0

Slow

Running

Current

47

% FLC

1

0

450

0

Braking

Current

48

% FLC

1

0

400

0

Advanced

Setup

Dual Ramp

29

No, Yes

No

Ramp Time

#2

32

Seconds

1

0

30

10

Initial Torque

#2

33

% LRT

1

0

90

70

Undervolt

Level

52

% Line

Voltage

1

0

99

0 (Off)

Undervolt

Delay

53

Seconds

1

0

99

0

Overvolt

Level

54

% Line

Voltage

1

0

199

0 (Off)

Overvolt

Delay

55

Seconds

1

0

99

0

Jam Level

56

% FLC

1

0

999

0 (Off)

Jam Delay

57

Seconds

10

0.0

10.0

0

Unbalance

Level

58

%

1

0

25

0 (Off)

Unbalance

Delay

86

Seconds

1

0

99

0

Rebalance

59

Off, On

Off

Underload

Level

60

% FLC

1

0

99

0 (Off)

Underload

Delay

61

Seconds

1

0

99

0

Phase

Reversal

62

Off, On

Off

Starts per

Hour

63

—1

0

99

0 (Off)

Restart

Attempts

64

1

0

5

2

Restart Delay

65

Seconds

1

0

60

0

ETM Reset

15

Off, On

Off

Parameter

Management

17

Ready, Default Init.

Recll Frm EE,Store In EE

Ready