Fault definitions – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 146

Advertising
background image

Diagnostics

9-3

Fault Definitions

Power Loss

Power loss indicates that an input power phase is not present. The
controller’s LCD display will identify the missing phase.

Note: If all three phases are absent when a start command is issued,

the LCD will display “Starting” without motor rotation.

Line Fault

Line fault with the affected phase displayed identifies three possible
pre-start conditions.

Phase loss

Load loss

Shorted SCR

Line fault with no phase indication is displayed when one of the
following conditions occurs while the SMC Dialog Plus controller is
in the run mode.

Phase loss

Load loss

Shorted SCR

Phase Reversal

Phase reversal is indicated when the incoming power to the SMC
Dialog Plus controller is in any sequence other than ABC. This pre-
start protective feature can be disabled.

Overvoltage and Undervoltage Protection

Overvoltage and undervoltage protection are user-defined as a
percentage of the programmed line voltage. The SMC Dialog Plus
controller continuously monitors the three supply phases. The
calculated average is then compared to the programmed trip level.

Phase loss, overvoltage, and undervoltage protection are disabled during braking operation.