Mounting, Dimensions – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 30

Advertising
background image

2-4

Installation

Mounting

The controller is convection cooled. Additionally, units rated for 97A
and above are fan cooled. It is important to locate the controller in a
position that allows air to flow vertically through the power module.
The controller must be mounted with heatsink fins in a vertical
plane and have a minimum of six inches (15 cm) free space above
and below the controller.

Dimensions

Figure 2.1 Dimensions: 24, 35, and 54 Amp Controllers

All dimensions are approximate and are not intended for manufacturing purposes. Refer to the nearest Allen-Bradley sales office for complete dimension drawings.