Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 93

Advertising
background image

Options

7-9

Figure 7.5 Typical Wiring Diagram for Two-wire Control or Programmable

Controller Interfacing

Customer supplied.

Refer to the controller nameplate to verify the rating of the control power input voltage.

Notes:

(1)

Refer to Chapter 3 for typical power circuits.

(2)

The OFF state leakage current for a solid-state device must be less than 6 mA.

Control Power ➁

Two-wire device ➀

11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30

Internal

Auxiliary
Contacts

SMC Dialog Plus

Control Terminals