Specifications, Appendix – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 164

Advertising
background image

Appendix

A

Specifications

Electrical Ratings

UL/CSA/NEMA

IEC

Power Circuit

Method of Connection

Motor in delta or star, SCRs between windings and supply

Number of Poles

Equipment designed for three phase loads only

Rated Operation Voltage (Ue)

200–480 VAC (–15%, +10%)
200–600 VAC (–15%, +10%)

200–415VY (–15%, +10%)
200–500VY (–15%, +10%)

Rated Insulation Voltage (Ui)

N/A

500V~

Rated Impulse Voltage (Uimp)

N/A

4000V

Dielectric Withstand

2200 VAC

2500V~

Repetitive Peak Inverse Voltage Rating

200–480 VAC: 1400V
200–600 VAC: 1600V

200–415~: 1400V

200–500V~: 1600V

Operating Frequency

50/60 Hz

50/60 Hz

Utilization Category

MG 1

AC-53a

Protection Against Electrical Shock

N/A

IP 00 (open device)

DV/DT Protection

RC Snubber Network

Transient Protection

Metal Oxide Varistors: 220 Joules @ 24–360A

220 Joules @ 480V, 500–1000A
300 Joules @ 480V, 500–1000A

Short Circuit Protection

SCPD Performance

Type 1

SCPD List

Maximum Fuse or Circuit Breaker

Device Operational

Current Rating (Ie)

Fault Current

Withstand Rating

(A rms sym)

24A

5000

80A

35A

5000

125A

54A

5000

200A

97A

10,000

350A

135A

10,000

500A

180A

10,000

600A

240A

18,000

700A

360A

18,000

1000A

500A

30,000

1200A

650A

30,000

1600A

720A

42,000

2000A

850A

42,000

2500A

1000A

85,000

3000A

Advertising