Control terminal designations, Grounding provision – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 52

Advertising
background image

3-6

Wiring

Control Terminal
Designations

As shown in Figure 3.9, the SMC Dialog Plus controller contains 20
control terminals on the front of the controller.

Figure 3.9 SMC Dialog Plus Controller Control Terminals

Do not connect any additional loads to these terminals. These “parasitic” loads may cause problems with operation, which may result in false starting and stopping.

When control power is absent from terminals 11 and 12, this contact will be normally open. Upon application of control power, the contact will take the state, normally
open or normally closed, as programmed.

Grounding
Provision

Provision for connecting a field installed grounding conductor is
provided on each controller. It is shown in Figure 3.10 and is located
on the heatsink. This symbol is the ground connection identification
symbol as defined by IEC Publication 417, Symbol 5019.

If the protective conductor is not connected to the heatsink, the
plating and/or paint must be cleaned from the four mounting holes or
four star washers (tooth lock washers) must be used.

Figure 3.10 Grounding Provision

Terminal

Number

Description

Terminal

Number

Description

11

Control Power Input

21

Not Used

12

Control Power Common

22

Not Used

13

Controller Enable Input

23

Not Used

14

Logic Ground

24

Not Used

15

Dual Ramp/Option Input

25

Converter Module Fanning Strip Connection

16

Start Input

26

Converter Module Fanning Strip Connection

17

Stop Input

27

Converter Module Fanning Strip Connection

18

Auxiliary Relay Common

28

Converter Module Fanning Strip Connection

19

N.O. Auxiliary Contact #1 (Normal/Up-to-speed)

29

N.O./N.C. Auxiliary Contact #3 (Normal/Fault)

20

N.C. Auxiliary Contact #2 (Normal/Up-to-speed)

30

N.O./N.C. Auxiliary Contact #3 (Normal/Fault)

11

21

12

22

13

23

14

24

15

25

16

26

17

27

18

28

19

29

20

30

Advertising