Remote i/o examples (cont.), Communication module bulletin 1202 scanport cable, 10 serial communications – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 119: Sw3, switches 4-8 (off)

Advertising
background image

8-10

Serial Communications

Remote I/O Examples (cont.)

Example #2 - SLC 500 Controller with Block Transfer

This example demonstrates a block transfer of the SMC Dialog Plus
controller’s metering group (parameters 1–11) to an SLC500. Many
of the selections shown are example-specific. Some changes by the
user may be necessary to apply the concepts of this example to a
specific application.

System Configuration

1203-GD1 Communication Module Switch Settings

The following information is provided to explain the required 1203-
GD1 communication module switch settings for this example. Refer
to the 1203-GD1 manuals for further details related to the switch
settings.

Example Information

The SMC Dialog Plus controller does not support Datalinks

SLC 5/02 or higher

1747-SN Scanner

Remote I/O Link

SMC Dialog Plus

Controller

1203-GD1

Re m I/O

Re m I/O ST S

Re m I/O AC T

H ea lth

SC AN b us ST S

FA ULT

2

SH

1

V +

V -

L 1

1

L 2

3

L 3

5

11

21

12

22

13

23

14

24

15

25

16

26

17

27

18

28

19

29

20

30

G

Communication Module

Bulletin 1202 SCANport Cable

Description

Switch Setting

SMC Rack Address:

0

SW1, Switches 1 & 2 (Not Used), Switches 3-8 (On)

Starting Group Address:

0

SW2, Switches 1 & 2 (On)

Last Rack:

Yes

SW2, Switch 3 (On)

Hold Last State:

Yes

SW2, Switch 4 (On)

Fault on Comm Loss:

Yes

SW2, Switch 5 (On)

Fault Controller:

Yes

SW2, Switch 6 (On)

RIO Baud Rate:

57k

SW2, Switches 7 & 8 (Off)

Block Transfer:

Yes

SW3, Switch 1 (On)

Logic Cmd/Status:

Yes

SW3, Switch 2 (On)

Reference/Feedback:

No

SW3, Switch 3 (Off)

Datalinks:

No

SW3, Switches 4-8 (Off)